Global Global Algérie Français Algeria English Angola Português Angola English Argentina Español Argentina English Australia English Austria Deutsch Austria English Azerbaijan English Azerbaijan Русский Bahrain English Bangladesh English Belgium English Belgium Français Belgium Nederlands Brazil Português Brazil English Bulgaria български Bulgaria English Cameroon English Cameroon Français Canada English Canada Français Chile Español Chile English China 中文 China 日本語 China English Colombia Español Colombia English Croatia English Czech Republic Čeština Czech Republic English Denmark English Djibouti English Ecuador Español Ecuador English Egypt English Estonia English Ethiopia English Finland Suomi Finland English France Français France English Georgia English Georgia Русский Germany Deutsch Germany English Ghana English Greece Ελληνικά Greece English Guatemala Español Guatemala English Hong Kong, China English Hong Kong, China 中文 Hungary Magyar Hungary English India English Indonesia English Iraq English Ireland English Italy Italiano Italy English Ivory Coast Français Ivory Coast English Japan 日本語 Japan English Jordan English Kazakhstan Русский Kazakhstan English Kenya English Kuwait English Kyrgyzstan Русский Kyrgyzstan English Latvia English Lithuania English Malaysia English Mauritius English Mauritius français (Maurice) Mexico Español Mexico English Moldova Română Moldova English Mongolia English Morocco English Morocco Français Mozambique Português Mozambique English Netherlands Nederlands Netherlands English New Zealand English Nigeria English Norway English Oman English Pakistan English Paraguay Español Paraguay English Peru Español Peru English Philippines English Poland Polski Poland English Portugal Português Portugal English Qatar English Republic of Korea 한국어 Republic of Korea English Romania Română Romania English Saudi Arabia English Serbia Српски Serbia English Singapore English Slovakia English Slovenia English South Africa English Spain English Spain Español Sri Lanka English Sweden English Switzerland Deutsch Switzerland Français Switzerland Italiano Switzerland English Tanzania English Thailand ไทย Thailand English Togo English Togo Français Tunisia English Tunisia Français Türkiye Türkçe Türkiye English Turkmenistan Русский Turkmenistan English Ukraine Українська Ukraine English United Arab Emirates English United Kingdom English Uruguay Español Uruguay English USA English Uzbekistan English Uzbekistan Русский Vietnam Tiếng Việt Vietnam English

Transformer oil chromatography analysis, commonly known as dissolved gas analysis (DGA), is the most widely used laboratory technique for detecting incipient faults in oil-immersed transformers and other electrical equipment. By separating and quantifying the gases dissolved in insulating oil using gas chromatography, engineers can identify overheating, partial discharge, and arcing long before catastrophic failure occurs. This guide explains the principle, sampling requirements, testing items, analytical methods, and interpretation standards behind professional transformer oil chromatography analysis.

Technical Overview

Transformer oil chromatography analysis, internationally referred to as dissolved gas analysis (DGA), is a condition-monitoring technique used to detect and diagnose internal faults in oil-filled electrical equipment. Power transformers are insulated with mineral insulating oil and cellulose-based solid insulation. When the equipment is subjected to abnormal thermal or electrical stress, the hydrocarbon molecules in the oil and the cellulose polymers in the paper decompose, generating characteristic gases such as hydrogen, methane, ethane, ethylene, acetylene, carbon monoxide, and carbon dioxide. Because these gases remain dissolved in the oil, their concentrations and relative proportions provide a reliable fingerprint of the fault type, location, and severity.

The gas generation mechanism is strongly temperature-dependent. Low-temperature overheating of the oil (roughly 150 to 300 degrees Celsius) mainly produces methane and ethane; higher-temperature hot spots (300 to 700 degrees Celsius) generate increasing amounts of ethylene; and arcing or hot spots above approximately 800 degrees Celsius produce acetylene. Hydrogen is the characteristic gas of partial discharge and corona activity. Thermal or electrical degradation of the cellulose insulation generates carbon monoxide and carbon dioxide. By tracking these gas signatures over time, transformer oil chromatography analysis makes it possible to identify developing faults months before they escalate into major failures, which is why DGA is often described as the single most effective diagnostic tool for in-service transformers.

The analytical process is governed by internationally recognized standards, including IEC 60567 (sampling and analysis of free and dissolved gases), IEC 60599 (interpretation of gas analysis results), ASTM D3612 (analysis of gases dissolved in electrical insulating oil by headspace sampling), and the corresponding national standards GB/T 17623 and GB/T 7252. Accredited third-party laboratories perform this testing with calibrated gas chromatography systems to ensure accurate, comparable results.

Testing Samples

Correct sampling is critical to the validity of transformer oil chromatography analysis. Oil samples are typically collected in gas-tight glass syringes or sealed amber bottles directly from the equipment drain valve, with every effort made to exclude air bubbles and atmospheric contamination. Depending on the scope of the assessment, the following sample types are routinely analyzed:

Main Tank Oil from Power Transformers

Oil is drawn from the bottom drain valve of the main tank while the transformer is in service or shortly after de-energization. A typical sample volume is 40 to 100 milliliters. The oil temperature, load condition, and sampling date must be recorded, because gas concentrations are interpreted against the operating state of the unit. This sample type forms the basis of routine DGA monitoring programs.

Oil from Shunt Reactors and On-Load Tap Changers

Shunt reactors are sampled and analyzed in the same manner as transformer main tanks. Oil from on-load tap changer (OLTC) compartments requires separate handling: arcing is a normal operating condition inside an OLTC, so acetylene and hydrocarbon levels are naturally high. Dedicated sampling prevents cross-contamination between compartments and misdiagnosis of results.

Oil from Instrument Transformers and Bushings

Current transformers, voltage transformers, and condenser bushings contain relatively small oil volumes. Because even a modest quantity of fault gas can represent a significant concentration in a small oil mass, chromatography analysis of these components is a sensitive indicator of partial discharge and low-energy faults, and is widely used in high-voltage substations.

Free Gas from Gas Relays

When a Buchholz or gas relay accumulates free gas, a sample of that gas can be collected in a gas-tight syringe and analyzed chromatographically. Comparing the composition of the free gas with the dissolved gas pattern in the oil helps confirm whether the gas originates from an internal fault or from external causes such as air ingress.

New Oil and Commissioning Baseline Samples

DGA is also performed on new oil before filling and on oil sampled immediately after commissioning. Establishing a baseline gas profile allows subsequent routine results to be evaluated as trends, greatly improving diagnostic confidence.

Testing Items

A routine transformer oil chromatography analysis quantifies the nine gases routinely monitored in mineral insulating oil, along with several derived diagnostic parameters:

  • Hydrogen (H2): the key gas for partial discharge, corona, and low-energy discharge faults.
  • Methane (CH4): indicates low-temperature thermal decomposition of the oil (roughly 150 to 300 degrees Celsius).
  • Ethane (C2H6): accompanies methane in low-temperature overheating of insulating oil.
  • Ethylene (C2H4): the characteristic gas of high-temperature thermal faults, typically 300 to 700 degrees Celsius and above.
  • Acetylene (C2H2): a marker of arcing and very high temperature hot spots above approximately 800 degrees Celsius; even trace amounts in a main tank warrant attention.
  • Carbon monoxide (CO): produced by thermal or electrical degradation of cellulose paper insulation.
  • Carbon dioxide (CO2): accompanies carbon monoxide from paper aging; the CO2/CO ratio helps distinguish normal aging from fault-related decomposition.
  • Oxygen (O2) and nitrogen (N2): evaluated to assess the effectiveness of the oil preservation system, sealing condition, and degree of air ingress.

In addition to individual gas concentrations, laboratories report calculated values such as total hydrocarbon content, total combustible gas content, absolute and relative gas generation rates, and the CO2/CO ratio. Gas generation rates, expressed in parts per million per day or per month, are often more diagnostic than single absolute values, because a steadily rising trend confirms an active, developing fault.

Testing Methods

Transformer oil chromatography analysis follows a structured workflow from sampling through interpretation, as specified in IEC 60567, IEC 60599, ASTM D3612, ASTM D3613, GB/T 17623, and GB/T 7252.

Sampling and Sample Handling

Oil is sampled into clean, dry glass syringes or sealing bottles through a flush-and-fill procedure at the drain valve, ensuring no headspace or air bubbles. Samples are transported upright, protected from light and temperature extremes, and analyzed as soon as practicable, ideally within a few days, to prevent gas loss or exchange through container walls.

Extraction of Dissolved Gases

Before chromatographic separation, the dissolved gases must be extracted from the oil. Common extraction techniques include vacuum degassing (partial-pressure extraction), static headspace equilibrium extraction, and dynamic stripping with a carrier gas. Each method aims for high and repeatable extraction efficiency so that measured gas concentrations accurately reflect the true dissolved gas content of the oil.

Gas Chromatographic Separation and Detection

The extracted gas mixture is injected into a gas chromatograph equipped with appropriate packed or capillary columns. A molecular sieve column separates hydrogen, oxygen, and nitrogen, while porous polymer columns separate methane, ethane, ethylene, acetylene, carbon monoxide, and carbon dioxide. Detection is typically performed with a dual-detector arrangement: a thermal conductivity detector (TCD) measures inorganic gases such as hydrogen, oxygen, and nitrogen, while a flame ionization detector (FID) measures hydrocarbons with high sensitivity. Carbon monoxide and carbon dioxide are passed through a nickel-catalyst methanizer, which converts them into methane so they can be quantified sensitively by the FID.

Calibration and Quality Control

The chromatograph is calibrated with certified standard gas mixtures of known concentration, and results are reported in microliters of gas per liter of oil, equivalent to parts per million by volume. Quality control measures include blank runs, duplicate extractions, calibration verification, and detection limits on the order of 0.1 ppm or better for acetylene, ensuring the reliability required for fault diagnosis.

Interpretation of Results

Once gas concentrations are quantified, fault diagnosis is performed using established interpretation methods. The key gas method associates the dominant gas with the probable fault type. Ratio methods, such as the Rogers ratios (CH4/H2, C2H2/C2H4, and C2H6/CH4) and the ratio tables of IEC 60599, classify faults as thermal or discharge-related. The Duval Triangle method plots the relative percentages of methane, ethylene, and acetylene on a triangular diagram divided into zones covering partial discharge, low- and high-energy discharge, and low-, medium-, and high-temperature thermal faults, as well as mixed fault zones. Because each method has limitations, experienced analysts apply several methods together, place the greatest weight on gas generation trends, and cross-check conclusions against electrical test data, oil quality test data, and the operating history of the equipment.

Applications

Transformer oil chromatography analysis supports asset management and reliability programs across the entire lifecycle of oil-filled electrical equipment:

  • Routine condition monitoring of in-service power transformers, shunt reactors, and instrument transformers in transmission and distribution networks.
  • Early detection of incipient faults such as winding overheating, core circulating currents, deteriorating bolted connections, partial discharge, and arcing beneath the oil surface.
  • Diagnosis following a gas relay alarm or trip, including analysis of free gas collected by the relay to confirm the presence and nature of an internal fault.
  • Acceptance testing and baseline profiling of newly delivered or newly commissioned transformers at factories and substations.
  • Condition-based maintenance planning, allowing utilities and industrial operators to prioritize repairs, schedule outages strategically, and defer unnecessary interventions.
  • Assessment of cellulose insulation aging through carbon monoxide and carbon dioxide trends, often complemented by furan compound analysis performed with high-performance liquid chromatography.
  • Support for load management decisions, life-extension studies, and root-cause investigations after equipment failures in power plants, wind farms, railways, data centers, and heavy industry.

FAQ

How often should transformer oil chromatography analysis be performed?

For most transmission-class transformers, annual DGA is a common baseline, with quarterly or monthly testing applied to extra-high-voltage, critical, or aging units. When results show abnormal gas levels or a rising trend, testing frequency is increased so the fault development can be tracked closely. Maintenance strategies based on IEC 60422 and GB/T 7252 provide guidance on intervals according to equipment rating, condition category, and importance.

What are typical attention values for dissolved gases?

Indicative attention levels often adopted for mineral-oil-filled power transformers include hydrogen at approximately 100 ppm, total hydrocarbons at approximately 150 ppm, and acetylene at roughly 1 to 5 ppm depending on voltage class, with carbon monoxide and carbon dioxide typically reviewed against limits in the range of several hundred and several thousand ppm respectively. Exact limits vary by standard, equipment type, and oil preservation system, and in all cases rising generation rates deserve more weight than a single absolute value.

Why is acetylene in transformer oil treated so seriously?

Acetylene forms at temperatures above roughly 800 degrees Celsius, which in a transformer almost always signifies arcing or a very severe hot spot. Because trace amounts are meaningful, laboratories calibrate their chromatographs to detect acetylene down to about 0.1 ppm, and even small concentrations in a main tank sample normally trigger intensified monitoring or an internal inspection.

Can DGA detect every transformer fault?

No. Transformer oil chromatography analysis excels at detecting thermal and discharge faults that generate gases, but it cannot directly reveal purely mechanical problems such as winding looseness or tap changer mechanism wear, and low-energy faults in equipment with very small oil volumes may evolve quickly. Best practice combines DGA with dielectric tests, oil quality analysis, furan analysis, partial discharge measurement, and physical inspection.

Why must oil samples be collected without air bubbles?

Air bubbles or headspace in the sampling container allow dissolved gases to escape and atmospheric gases to dissolve into the oil, distorting the measured concentrations of hydrogen, oxygen, nitrogen, and carbon dioxide. For this reason, standards such as IEC 60567 and ASTM D3613 specify gas-tight glass syringes and a careful flush-and-fill sampling procedure.

Do elevated carbon monoxide and carbon dioxide always indicate a fault?

Not necessarily. Both gases are produced by normal cellulose aging, and their absolute levels rise gradually over the service life of a transformer. Analysts examine the CO2/CO ratio and long-term trends: abnormally low ratios or sudden step changes often indicate that the paper insulation is involved in a thermal or electrical fault, and furan analysis can be added to estimate the degree of polymerization and remaining paper life.

How quickly should samples be analyzed after sampling?

Samples should reach the laboratory and be analyzed as soon as possible, ideally within a few days of sampling. During transport they must be kept upright, sealed, and protected from light and heat to preserve the original dissolved gas equilibrium and ensure representative results.